Galvanic Isolator vs Isolation Transformer: Which One Does Your Boat Need?

Technician checking breakers on a yacht's AC distribution panel

Home / Articles / Galvanic Isolator vs Isolation Transformer: Which One Does Your Boat Need?

A galvanic isolator is a small diode unit in the shore power green ground wire that blocks low-level galvanic current, and BoatUS calls it a practical choice for many boats. An isolation transformer removes every wired link to the dock and, properly connected, also prevents AC stray-current corrosion of aluminum outboards, but it is heavy and expensive.

Galvanic isolator vs isolation transformer: what is the difference?

A galvanic isolator filters the green ground wire to the dock, while an isolation transformer replaces the wired connection to the dock with a magnetic one.

Every boat on marina shore power is connected to every other plugged-in boat through the green grounding wire, which can form a galvanic cell between them. A galvanic cell forms when dissimilar metals are connected through an electrolyte such as seawater. Our guide to electrolysis on boats covers the damage.

  • Galvanic isolator: wired in series in the green ground conductor only, between the shore power inlet and the main panel grounding bus.
  • Isolation transformer: installed between the shore power inlet and the main AC panel, passing power by magnetic induction, with no hard-wired connection to the dock.

What is a galvanic isolator and how does it work?

A galvanic isolator is essentially a blocking diode assembly that stops low-level DC on the green ground wire, isolating the boat from the dock and neighboring boats.

The diodes conduct only above a threshold: BoatUS puts it at about 1.2 V DC and says almost all galvanic voltages are below it; Boating Magazine describes about 1 V as the most an isolator blocks.

A galvanic isolator keeps the ground wire continuous, so AC fault current can still flow back to the dock pedestal and trip the breaker. Better isolators add a capacitor so they keep blocking galvanic DC when a small AC leakage current is on the ground wire.

A galvanic isolator will not prevent AC stray-current corrosion of aluminum outboards, and Marine How To says it does not block stray-current leaks above about 1.2 V.

Fail-safe isolators and status monitors

A fail-safe galvanic isolator fails closed: if it fails, the boat loses galvanic protection but keeps its safety ground to shore.

Older isolators could fail open and drop the ground; isolators on new boats since 2011 fail closed. BoatUS advises an isolator with a UL marine rating, because those units are fail-safe. BoatUS summarizes ABYC guidelines: rated for system amperage, usually 30 or 50 A, hard-wired with no friction-type connections, and unable to open-circuit the safety ground.

Sources disagree on whether a fail-safe unit still needs a monitor. At the time of writing, ProMariner says its ProSafeFS isolators are UL certified to ABYC A-28 and need no dedicated status monitor, which non-fail-safe isolators require. BoatUS advises a remote monitor panel for an isolator installed out of sight, because isolators can stop working after major electrical faults or nearby lightning.

When would you use an isolation transformer?

An isolation transformer is typically used on larger boats and aluminum boats, and it also protects the boat's AC system from shoreside power surges.

  • Full separation: Victron says an isolation transformer removes all electrical continuity with shore power and makes galvanic isolators and polarity alarms unnecessary.
  • Leakage stays aboard: with the secondary wired correctly, leakage current returns to the transformer through the green ground conductor, not through the water.
  • Polarity and voltage: the transformer is self-polarizing, so reversed dock wiring still gives correct AC aboard, and Victron's 1:1.05 ratio boosts output 5% for low marina voltage.
  • Travel: Victron's unit converts 230 V to 120 V and 115 V to 240 V and runs on 50 Hz or 60 Hz, but cannot convert frequency. At the time of writing, its 3600W Auto detects 115 or 230 V input and is rated 32 A at 115 V or 16 A at 230 V.

Victron requires a GFCI on the transformer's AC output, with the output neutral linked to output earth and the boat's metal parts. Victron also says that when the boat is out of the water, its earth conductor must be connected directly to shore earth, using the transformer's jumper.

What are the disadvantages of using an isolation transformer?

An isolation transformer is heavy, takes significant space, gets hot while running and is expensive, while galvanic isolators are small and relatively inexpensive.

Published weights vary: BoatUS has put typical units at 80-200 lb and a typical 30-amp unit at about 60-70 lb. At the time of writing, Victron lists its 3600W Auto at 21.7 kg (about 48 lb), and ProMariner lists its fail-safe isolators at 3 lb and 3.7 lb.

A 30-amp isolation transformer must be installed within 10 feet of the shore power inlet, and small boats may not tolerate the weight. Two shore inputs need two transformers, doubling weight and cost.

Where does an ELCI fit in?

An ELCI (equipment leakage circuit interrupter) is a separate device at the shore cord inlet that opens the circuit if leakage reaches 30 mA.

ELCI protection has been in ABYC standards since 2011. ABYC E-11, as quoted in 2013, set a maximum trip level of 30 mA and trip time of 100 ms; the current text may differ.

An ELCI prevents shocks to swimmers in a fault and gives some protection against AC current corrosion. An ELCI does not protect against faults upstream of it, so inspect the inlet and wiring ahead of it closely. Before installing an ELCI, triple-check that shore cord, generator and inverter circuits are secured off.

Which one does your boat need?

A fail-safe galvanic isolator suits many boats on shore power, while isolation transformers are typically used on larger boats and aluminum boats. Of the two, only a transformer prevents AC stray-current corrosion of aluminum outboards.

Boat and how it is usedDevice the sources point toTrade-off
Fiberglass boat on one 30-amp or 50-amp cordFail-safe galvanic isolator sized to the cordNo protection from AC stray-current corrosion
Aluminum boat, or boat with an aluminum outboardIsolation transformerHeavy, bulky, runs hot, expensive
Small boat with little weight margin near the inletGalvanic isolator (ProMariner lists 3-3.7 lb)Transformer weight may be too much
Larger boat on 100-amp shore powerIsolation transformer, in Ed Sherman's viewSpace, weight and heat
Boat with two shore inletsOne isolator, or one transformer, per inletTwo transformers double weight and cost
Boat moving between 120 V and 240 V docksVoltage-converting isolation transformer such as Victron'sVictron's cannot convert 50 Hz to 60 Hz

What to check before you buy

The choice starts with the boat's shore power layout and underwater metals.

  • Shore cord amperage and number of shore inlets.
  • A UL marine rating on any galvanic isolator.
  • Aluminum hull or outboard in the water.
  • Space and weight capacity within 10 feet of the inlet for a transformer.
  • Whether the isolator will sit out of sight and need a remote monitor panel.
  • Whether the boat already has an ELCI.

How to install and test a galvanic isolator

A galvanic isolator goes in series in the green ground conductor with all power secured, then gets a multimeter test.

  1. Turn off all AC breakers at the pedestal and aboard, unplug the shore cord at both ends, and secure any inverter.
  2. Match the isolator to the cord: 30-amp cord, 30-amp isolator; 50-amp cord, 50-amp isolator; one per inlet.
  3. Use a UL marine-rated unit and hard-wired connections, never friction-type connectors.
  4. Wire the isolator in series in the green ground conductor between the shore power inlet and the main panel grounding bus.
  5. Fit a remote monitor panel if the isolator sits out of sight.
  6. With breakers off and the cord unplugged at the dock end, set a multimeter to diode check: black lead on the shore cord ground, red lead on the boat's green ground bus.
  7. Read the meter: a good isolator climbs slowly to about 1 V (about 1000 mV) and stops; discharge the capacitor and repeat with the leads reversed.

Common mistakes with galvanic isolators and isolation transformers

Cutting the green ground to stop corrosion is an extremely dangerous mistake: GFCIs will not work and breakers will not trip on a short to the boat's metal.

  • Removing the green ground, which lets an AC fault energize equipment cases, the boat or the water with deadly results. Even a few milliamps of AC in the water can paralyze a swimmer's muscles and cause drowning.
  • Working on a transformer or shore power wiring while it is still connected to a power source.
  • Expecting a galvanic isolator to stop AC stray-current corrosion of an aluminum outboard.
  • Fitting one isolator for two inlets, or one rated below the shore cord.
  • Leaving out the GFCI and neutral-to-earth link Victron requires on the transformer output.

What can you do yourself, and when do you need a marine electrician?

A boat owner can check ratings, watch the monitor panel and run the diode test unplugged; AC wiring work belongs with a marine electrician.

With the boat unplugged and any inverter secured, an owner can compare cord and isolator amperage, watch the remote monitor, and run steps 6 and 7. Call a marine electrician for any isolation transformer and its output GFCI, for an ELCI, and for faults between the inlet and the ELCI.

How eMarine Systems can help

eMarine Systems works on shore power and corrosion problems dockside at marinas across Miami-Dade, Broward and Palm Beach counties.

Our shore power repair work covers the inlet-to-panel circuit where an isolator or transformer goes, and a corrosion testing survey helps show whether the problem is galvanic or stray current. Each project starts with a power demand analysis, system sizing and compatibility checks, with support after commissioning. eMarine works with Victron among other brands and is an ABYC member.

eMarine does not do hull, fiberglass, engine mechanical or propeller work. Cost is quoted after an onboard inspection; call (954) 520-2055.

Frequently asked questions

Do I need both a galvanic isolator and an isolation transformer?

No, Victron says a true isolation transformer makes a galvanic isolator unnecessary. A polarity transformer, which keeps the shore ground wire, does need an isolator added.

Can an isolation transformer convert 50 Hz dock power to 60 Hz?

No, Victron's isolation transformer cannot convert frequency between 50 Hz and 60 Hz. It runs on either frequency and can convert 230 V to 120 V.

Does a galvanic isolator stop stray-current corrosion?

No, a galvanic isolator will not prevent AC stray-current corrosion of aluminum outboards; a properly connected isolation transformer will.

Does a boat with an isolation transformer still need an ELCI?

Not under the ABYC E-11 text as quoted in 2013, which exempts boats with an isolation transformer within 10 feet (3 m) of the inlet. That wording may have changed, so check the current standard.